Please note: This is a B2B online shop!
This offer is exclusively for business customers, tradesmen and freelancers. Consumers cannot buy here. All prices are net prices and do not include VAT and shipping costs.
| Nominal power | 3.0 kW (3 HP) |
| Nominal voltage | 380-480 V (+/-10%) | 3-phase |
| Max. output current | 7.2 A |
| Frame size | 3 |
| Dimensions H x W x D | 192 x 90 x 132 mm (7.56 x 3.54 x 5.20 in) |
| Weight | 1.0 kg (2.2 lb) |
Easy To InstallThe sleek curved design of Commander S optimises component layout for a small footprint and easy access to terminals. The click-on/click-off DIN rail mount makes installation remarkably easy. |
|
Easy To UseUsing our new Marshal app (Android/iOS) your drive can be configured in under 60 seconds. |
|
ReliableDurability is at the core of Commander S design, guaranteeing performance throughout its whole lifetime. |
|
Cost EffectiveEquipped with unique features designed to save you time, energy and money. |
| Voltage | single-phase 100 and 200 VAC three-phase 200 and 400 VAC |
| Power Range | 0.18 to 4 kW / 0.25 to 5 hp |
| Duty rating | Heavy duty |
| Input Frequency | 50/60 Hz |
| Output Frequency | 0 to 300 Hz |
| Switching Frequency | 4 kHz or 12 kHz |
| Motor Control | Linear V to F, Square V to F, Resistance Compensation |
| Stopping Modes | Coast, Ramp, Ramp & DC Injection Braking, DC Injection Braking with 0 Hz detect, Timed DC Injection Braking, Distance Stop |
| Communications | RJ45 for Modbus RTU, NFC for app interface |
| Analogue | 2 x Analogue input 1 x Analogue output |
| Digital | 4 x Digital input 1 x Digital input / output |
| Relay | 1 x Relay (single pole, double throw relay) |
| Approvals | CE, UKCA, cUL, C-Tick, EAC, KC |
| Product Safety Standards | IEC/EN/KN/UL 61800-5-1, CSA C22.2 No.274, GB12668.501-2013 |
| Emission Compliance | Category C3 (internal filters only) Category C1 & C2 (external EMC filters) Category C1, (internal filters only, selected 1Φ 200 V variants) |
| IP Rating | IP20 |
| Mounting | Click-on/Click-off DIN rail mounting Screw mounting 0 mm side by side |
| Ambient temperature | Operation without power reduction: -10 °C to 40 °C (14 °F to 104 °F) Operation with power reduction: -10 °C to 60 °C (14 °F to 140 °F) (14 °F to 140 °F) Storage -40 °C to 60 °C (-40 °F to 140 °F) |
| Offline Programming | Program the drive while it is still in the box |
| Cloning | Clone parameter sets from one drive to another |
| Faststart | Guided commissioning and motor rotation verfication test |
| Guided Diagnostics | Easy fault finding |
| Parameter File Storage | Save prameter files to the device or cloud for future use |
| Share Project Configuration | Share to colleagues or to EPA Technical Support for diagnostics |
| PDF Parameter Set | Useful for sharing parameter sets for quick review |
| Wiring Diagram | Automatically generate a printable pdf of a custom wiring diagram for your installation |
| Non-Default Parameter | Show the parameters that have been changed from their default setting |
| Favourite Parameters | Favourite parameters visited often |
| Guides and Manuals | Quick access to drive documentation |
| Control Word Control | ✓ |
| Cloning | ✓ |
| Serial Baud Rate | 600 to 115.000 bps |
| Modbus Rtu Protocol | 8.2NP, 8.1NP, 8.1EP, 8.1OP |
| Selectable References | 4 |
| Jog Reference | ✓ |
| Up / Down % Reference (Motorised Pot) | ✓ |
| Bi-Polar Reference | ✓ |
| Preset Speeds | 4 |
| Skip Frequencies | 1 |
| Skip Frequencies Dead Band | ✓ |
| Local/Remote | ✓ |
| S-Ramp | ✓ |
| Acceleration Rates | 2 |
| Deceleration Rates | 2 |
| Frequency Input Reference (Pulse Train) | 0 Hz to 100 kHz |
| Run Reverse | ✓ |
| PID Controller | PI Control |
| PID Feedforward | ✓ |
| PID Threshold Detector | ✓ |
| PID Slew Rate | ✓ |
| Reference Configuration | ✓ |
| Run/Stop Configuration | ✓ |
| Input Scaling | 4-point |
| Run Permit (Latching Run) | ✓ |
| Limit Switches | ✓ |
| Control Mode: Linear V to F | ✓ (Definable Boost) |
| Control Mode: Square V to F | ✓ (Definable Boost) |
| Control Mode: Resistance Compensation | ✓ |
| Low Energy Mode (Dynamic V to F) | ✓ |
| Motor Stability Optimiser | ✓ |
| Slip Compensation | ✓ |
| Auto-Tune: Static | ✓ |
| Switching Frequency | 4 or 12 kHz |
| Catch An Already Spinning Motor | ✓ |
| Stop Mode: Ramp | ✓ |
| Stop Mode: Coast | ✓ |
| Stop Mode: Distance Stop | ✓ when selected it stops in the same distance from any speed based on the programmed deceleration rate |
| DC Injection Braking | ✓ |
| Supply Loss Detection | ✓ |
| Programmable Output Current Limit | ✓ |
| Diagnostics | ✓ |
| Error History Log | 4 |
| Parameters Saved On Error | 3 (Selectable) |
| Auto-Reset After Trip | ✓ |
| Power Loss Ride Through | ✓ |
| Security | 4-digit PIN protection |
| Cooling Fan | Fixed Speed (No fan on S100-01x13 or S100-01x23 drives) |
Fan, Pump, Compressor Applications
|
|
Moving ApplicationsConveyors, Treadmills, Automatic Doors & Barriers
|
|
Processing ApplicationsMixers, Crushers, Agitators, Centrifuges, Kneaders, Spinning & Braiding Machines for Textile
|
{{.}}
{{/content}}{{{.}}}